• 1

PowerAgent Online LCD UPS 1008/2016/3024

   

Online UPS Series

  • True double-conversion
  • Wide input voltage range (110-300 VAC)
  • Input power factor correction 0.99
  • Output Power Factor 0.8
  • 50Hz/60Hz frequency converter mode
  • Charger capacity expansion to 8A for long-run models
  • Emergency power off function (EPO)
  • Eco mode operation for energy saving (ECO)
  • Generator compatible
  • SNMP+USB+RS-232 multiple communications
  • Smart battery charger design for optimized battery performance
  • Selectable output voltage: 208-240VAC, 110-127VAC
  • Accessory: External maintenance bypass switch & SNMP card

Specifications

MODELPowerAgent 1008
Online LCD (L)
PowerAgent 2016
Online LCD (L)
PowerAgent 3024
Online LCD (L)
Back Plan4 IEC output8 IEC output6 IEC outpu
CAPACITY1000 VA / 800 W2000 VA / 1600 W3000 VA / 2400 W
INPUT
Voltage
Range
Low Line Transfer160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or
80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 %
( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
Low Line Comeback175 VAC ± 5 % or 85 VAC ± 5 %
High Line Transfer300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback290 VAC ± 5 % or 145 VAC ± 5 %
Frequency40 Hz ~ 70 Hz
PhaseSingle phase with ground
Power Factor≧ 0.99 @ 220-230 VAC (input voltage)
OUTPUT
Output Voltage (Batt. Mode)± 3%
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
TCurrent Crest Ratio3:1
Harmonic Distortion≦ 3 % THD (Linear Load),
≦ 6 % THD (Non-linear Load)
≦ 4 % THD (Linear Load)
≦ 7 %THD (Non-linear Load)
Transfer
Time
AC Mode to Batt. ModeZero
Inverter to Bypass4 ms (Typical)
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY
AC Mode85%88%
Battery Mode83%
BATTERY
Standard
Model
Battery Type12 V / 7 Ah12 V / 7 Ah12 V / 9 Ah
Numbers366
Typical Recharge Time4 hours recover to 90% capacity
Charging Current (max.)1.0 A
Charging Voltage41.0 VDC ± 1%82.1 VDC ±1%
Long-run
Model
Battery TypeDepending on the capacity of external batteries
Numbers
Charging Current (max.)8.0A
Charging Voltage41.0 VDC ± 1%82.1 VDC ±1%
INDICATORS
LCD PanelUPS status, Load level, Battery level, Input/Output voltage,
Discharge timer, and Fault conditions
LED PanelSixteen LEDs indicating UPS status, Load level, Battery level,
overload, fault, and programmable outlet information
ALARM
Battery ModeSounding every 4 seconds
Low BatterylSounding every second
OverloadSounding twice every second
FaultContinuously sounding
PHYSICAL
Tower
Case
Standard
Model
Dimension,
D X W X H (mm)
397 X 145 X 220421 X 190 X 318
Net Weight (kgs)132628
Long-run
Model
Dimension,
D X W X H (mm)
397 X 145 X 220421 X 190 X 318
Net Weight (kgs)71313
Rack
Case
Standard
Model
Dimension,
D X W X H (mm)
420x438x88[2U]580x438x133[3U]
Net Weight (kgs)162931
Long-run
Model
Dimension,
D X W X H (mm)
420x438x88[2U]580x438x133[3U]
Net Weight (kgs)101717
ENVIRONMENT
Operation Humidity20-90 % RH @ 0- 40°C (non-condensing)
Noise LevelLess than 45dB @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows 98/2000/2003/XP/Vista/2008,
Windows 7, Linux, and MAC
Optional SNMPPower management from SNMP manager and web browser
* * Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output
voltage is adjusted to 208VAC.
* L means long-run model