Online UPS Series
|
| MODEL | 1K (L) | 1.5K (L) | 2K (L) | 3K (L) | ||
| CAPACITY | 1000 VA / 800 W | 1500 VA / 1200 W | 2000 VA / 1600 W | 3000 VA / 2400 W | ||
| INPUT | ||||||
| Voltage Range | Low Line Transfer | 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 % ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0) | ||||
| Low Line Comeback | 175 VAC ± 5 % or 85 VAC ± 5 % | |||||
| High Line Transfer | 300 VAC ± 5 % or 150 VAC ± 5 % | |||||
| High Line Comeback | 290 VAC ± 5 % or 145 VAC ± 5 % | |||||
| Frequency | 40 Hz ~ 70 Hz | |||||
| Phase | Single phase with ground | |||||
| Power Factor | ≧ 0.99 @ 220-230 VAC (input voltage) | |||||
| OUTPUT | ||||||
| Output Voltage (Batt. Mode) | ± 3% | |||||
| Frequency Range (Synchronized Range) | 47 ~ 53 Hz or 57 ~ 63 Hz | |||||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz | |||||
| Current Crest Ratio | 3:1 | |||||
| Harmonic Distortion | ≦ 3 % THD (Linear Load), ≦ 6 % THD (Non-linear Load) | ≦ 4 % THD (Linear Load) ≦ 7 %THD (Non-linear Load) | ||||
| Transfer Time | AC Mode to Batt. Mode | Zero | ||||
| Inverter to Bypass | 4 ms (Typical) | |||||
| Waveform (Batt. Mode) | Pure Sinewave | |||||
| EFFICIENCY | ||||||
| AC Mode | 85% | 88% | ||||
| Battery Mode | 83% | |||||
| BATTERY | ||||||
| Standard Model | Battery Type | 12 V / 7 Ah | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah | |
| Numbers | 3 | 3 | 6 | 6 | ||
| Typical Recharge Time | 4 hours recover to 90% capacity | |||||
| Charging Current (max.) | 1.0 A | |||||
| Charging Voltage | 41.0 VDC ± 1% | 82.1 VDC ±1% | ||||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | ||||
| Numbers | ||||||
| Charging Current (max.) | 8.0A | |||||
| Charging Voltage | 41.0 VDC ± 1% | 82.1 VDC ±1% | ||||
| INDICATORS | ||||||
| LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||
| LED Panel | Sixteen LEDs indicating UPS status, Load level, Battery level, overload, fault, and programmable outlet information | |||||
| ALARM | ||||||
| Battery Mode | Sounding every 4 seconds | |||||
| Low Battery | Sounding every second | |||||
| Overload | Sounding twice every second | |||||
| Fault | Continuously sounding | |||||
| PROTECTION | ||||||
| Full Protection | Overcharge, discharge, short circuit, and thermal protection | |||||
| PHYSICAL | ||||||
| Rack Case | Standard Model | Dimension, D X W X H(mm) | 420x438x88[2U] | 580x438x133[3U] | ||
| Net Weight (kgs) | 16 | 17 | 29 | 31 | ||
| Long-run Model | Dimension, D X W X H(mm) | 420x438x88[2U] | 580x438x133[3U] | |||
| Net Weight (kgs) | 10 | 10 | 17 | 17 | ||
| ENVIRONMENT | ||||||
| Operation Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | |||||
| Noise Level | Less than 45dB @ 1 Meter | |||||
| MANAGEMENT | ||||||
| Smart RS-232/USB | Supports Windows 98/2000/2003/XP/Vista/2008, Windows 7, Linux, and MAC | |||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||
| * Product specifications are subject to change without further notice | ||||||