Offline UPS Series
|
| MODEL | PowerAgent 424 Offline | PowerAgent 636 Offline | PowerAgent 848 Offline | |
| CAPACITY | 400 VA / 240 W | 600 VA / 360 W | 800 VA / 480 W | |
| INPUT | ||||
| Voltage | 110/120 VAC or 220/230/240 VAC | |||
| Acceptable Voltage Range | 90 – 145 VAC or 180 – 270 VAC | |||
| Voltage Range | Low Line Transfer | 90 ± 5% or 180 ± 5 % | ||
| Low Line Comeback | 95 ± 5% or 190 ± 5% | |||
| High Line Transfer | 145 ± 5% or 270 ± 5% | |||
| High Line Comeback | 140 ± 5% or 260 ± 5% | |||
| Frequency | 50Hz or 60Hz (Auto sensing) | |||
| OUTPUT | ||||
| Output Voltage (Batt. Mode) | 120VAC or 230 VAC ± 10% | |||
| Frequency Range (Batt. Mode) | 50Hz or 60Hz ± 1Hz | |||
| Transfer Time (Typical) | 2~6 ms | |||
| Waveform (Batt. Mode) | Simulated sine wave | |||
| BATTERY | ||||
| Battery Type & Number | 12 V/ 4.5 Ah x 1 | 12 V / 7 Ah x 1 | 12 V / 9 Ah x 1 | |
| Backup Time (one-PC load @100W) | 5~8 min. | 10~15 min. | 15~20 min. | |
| Typical Recharge Time | 8 hours recover to 90% capacity | |||
| INDICATORS | ||||
| AC Mode | Green lighting | |||
| Battery Mode | Green flashing every 10 seconds | |||
| Low Battery (Batt. Mode) | Green flashing every second and red lighting | |||
| Fault | Red lighting | |||
| ALARM | ||||
| Battery Mode | Sounding every 10 seconds | |||
| Low Battery (Batt. Mode) | Sounding every second | |||
| Fault | Continuously sounding | |||
| PROTECTION | ||||
| Full Protection | Overcharge, discharge, short circuit, and thermal protection | |||
| PHYSICAL | ||||
| Dimension, D X W X H (@ vertically stand) | 228 x 82.5 x 207 (mm) | |||
| Net Weight (kgs) | 2.2 | 2.7 | 3.1 | |
| OPERATING ENVIRONMENT | ||||
| Humidity | 0-90 % | |||
| Temerature | 0- 40°C (non-condensing) | |||
| * Product specifications are subject to change without further notice | ||||